ANALYSIS OF OVERVOLTAGE IN NONHOMOGENEOUS DISTRIBUTION CABLE GRIDS

Authors

  • A.V. Korzhov South Ural State University, Chelyabinsk, Russian Federation
  • O.V. Volkov Production department “Central electrical grids”, OJSC IDGC of Urals – Chelyabenergo branch, Chelyabinsk, Russian Federation
  • Yu.V. Korovin South Ural State University, Chelyabinsk, Russian Federation

DOI:

https://doi.org/10.14529/power200103

Keywords:

cable lines, overvoltage, insulation, distribution grid development, reliability

Abstract

Overvoltage in 6 (10) kV cable lines is one of the factors that have the strongest impact on the grid reliabi­lity.The paper discusses the resultsof testing the lengthwise distribution of overvoltage values in a typical section of a 10 kV distribution cable grid as induced by a single phase-to-ground fault; it also presents a method for minimizing such overvoltage.

Tests were run by simulation in ATPDraw. The cable-grid ATP model was based on elements with distributed reactive and active parameters. Cable-line overvoltage was found to change significantly depending on the configuration and design choices of cable types and cross-section values. Dead-end feeders had maximum overvoltage at the very end, where the research team observed both monotonic increase in overvoltage towards the end, and local maxima. In case where the line was not a dead end, maximum overvoltage was observed towards, but not at the end. Maximum overvoltage in a grid was found to correlate with the cable cross-sections.

The practical output of this research is guidelines on how to optimize the design for further cable grid development by minimizing the factor of projected overvoltage. The paper proposes visualizing the results as diagrams showing changes in maximum overvoltage along cable lines. Plotting such diagrams when designing, operating, or upgrading a grid will help pre-identify the most vulnerable points of cable lines where overvoltage could cause insulation failure. The paper shows that the best grid design and the worst grid design may differ by > 12% in peak overvoltage.

Downloads

Download data is not yet available.

References

Fessol F.N., Ariffin A. Mohd., Illias H. A. Influence of Underground Cable Insulation Parameters on Tran-

sient Overvoltages. IEEE 7th International Power Engineering and Optimization Conference. Langkawi, Malay-

sia, 2013, pp. 362–365. DOI: 10.1109/peoco.2013.6564573

Korzhov A.V. [Investigation of the influence of an alternating magnetic field on the intensity of partial

discharges in models simulating the insulation of a power cable]. Cables and Wires, 2013, no. 1 (338), pp. 8–13. (in Russ.)

Leonov V.M., Peshkov I.B., Ryazanov I.B., Kholodnyy S.D. Osnovy kabel'noy tekhniki: uchebnik dlya

stud. vysshikh uchebnykh zavedeniy [Fundamentals of cable technology: a textbook for students. higher education institutions]. Moscow, Akademiya Publ., 2006. 432 p.

Pravila ustroystva elektroustanovok [Rules for the installation of electrical installations]. 7th ed. St. Petersburg, UVISIZ, 2005.

Shuin A.V., Solodov S.V. Ob effektivnosti ogranicheniya perenapryazheniy pri dugovykh zamykaniyakh

na zemlyu razlichnykh rezhimov zazemleniya neyttrali elektricheskikh setey 6–35 kV [On the effectiveness of over-

voltage limitation during arc faults to earth of various modes of neutral grounding of electric networks of 6–35 kV].

Available at: http://ispu.ru/files/str._71-75.pdf (accessed 10.01.2019).

ATPDRAW version 5.6 for Windows 9x/NT/2000/XP/Vista Users' Manual. Available at:

http://www.elkraft.ntnu.no/atpdraw/ATPDMan56.pdf (accessed 10.01.2019).

Shafiee M., Vahidi B., Hosseinian S.H., Jazebi S. Using Artificial Neural Network to Estimate Maximum

Overvoltage on Cables with Considering Forward and Backward Waves. Universities Power Engineering Conference, 2008. DOI: 10.1109/upec.2008.4651620

Karapetyan I.G., Faibisovich D.L., Shapiro I.M. Spravochnik po proyektirovaniyu elektricheskikh setey

[Handbook for the design of electrical networks]. 4th ed., Revised. and add. Moscow, ENAS Publishing House, 2012. 376 p.

Goryunov I.T., Lyubimov A.A. (Ed.) Spravochnik po elektricheskim setyam 0,4–35 kV i 110–550 kV

[Handbook of electrical networks 0.4–35 kV and 110–550 kV]. Moscow, Papyrus Pro Publ., 2004. 688 p.

Haiqing Niu, Xin Zhou, Yao Zhang, Xiaobing Wang, Yinxia Shi, Yuxiang Xu. Parameter Analysis and

Research on Sheath Lightning Overvoltage of Single-Core Cable. Power and Energy Engineering Conference, 2009. DOI: 10.1109/appeec.2009.4918584

Published

2019-01-20

How to Cite

[1]
Korzhov, A., Volkov, O. and Korovin, Y. 2019. ANALYSIS OF OVERVOLTAGE IN NONHOMOGENEOUS DISTRIBUTION CABLE GRIDS. Bulletin of the South Ural State University series "Power Engineering". 20, 1 (Jan. 2019), 22–29. DOI:https://doi.org/10.14529/power200103.

Most read articles by the same author(s)