INCREASING ELECTRICAL SAFETY OF THE 10/0.38 kV NETWORK DUE TO CLARIFICATION OF THE SETTINGS OF PROTECTION DE-VICES IN THE EVENT OF THE 10 kV OVERHEAD LINE WIRE BREAK

Authors

  • A.V. Khlopova South Ural State University
  • A.N. Gorozhankin South Ural State University

DOI:

https://doi.org/10.14529/power240111

Keywords:

broken wire, 10 kV overhead line, negative sequence voltage, setting of protection device, electrical safety

Abstract

Translator        

 

A wire break is a common accident in distribution networks operating with an isolated neutral. Failure to shut down such an emergency situation results in a risk of electric shock. For proper operation of protection devices in the event of a wire break, it is necessary to select the correct setting of the information parameter. It is known that the negative sequence voltage can serve as such a parameter. The paper presents the results of studies of the influence of various operating modes of the 10/0.38 kV electrical network (both emergency and normal) on negative sequence voltage changes. The influence of the fault location and the parameters of the 10/0.38 kV network on the negative sequence voltage was also studied in order to clarify the negative sequence voltage setting for protection devices that respond to a wire break in the 10 kV overhead line. This will allow minimizing false alarms and increasing electrical safety in the 10 kV network.

Downloads

Download data is not yet available.

Author Biographies

A.V. Khlopova, South Ural State University

Translator        

 

 

A.N. Gorozhankin, South Ural State University

Translator        

 

 

References

Григорьев А.В., Селивахин А.И., Сукманов В.И. Защита сельских электросетей. Алма-Ата: Кайнар, 1984. 128 с.

Манилов А.М. Защита сети напряжением 6–35 кВ при разрыве фазы и падении провода на землю // Энергетик. 2003. № 11. С. 22–23.

Рыбаков Л.М., Столяров С.В., Наумов Е.Н. Техническое состояние сетей 10 кВ // Электрика. 2002. № 2. С. 19–21.

Development of open (Broken) conductor detection system for high resistivity areas / S.H. Al-Ghannam, Y. Khan, U. Ahmad et al. // 2017 Saudi Arabia Smart Grid (SASG). Jeddah, Saudi Arabia, 2017. P. 1–8. DOI: 10.1109/SASG.2017.8356491

Catching falling conductors in midair – detecting and tripping broken distribution circuit conductors at pro-tection speeds / W. O'Brien, E. Udren, K. Garg et al. // 2016 69th Annual Conference for Protective Relay Engi-neers (CPRE). College Station, TX, USA, 2016. P. 1–11. DOI: 10.1109/CPRE.2016.7914881

Pongthavornsawad A., Rungseevijitprapa W. Broken Conductor Detection for Overhead Line Distribution System // 2011 Asia-Pacific Power and Energy Engineering Conference. Wuhan, China, 2011. P. 1–4. DOI: 10.1109/APPEEC.2011.5749066

Ершов А.М., Хлопова А.В. О выборе информационного параметра и места установки защиты при обрыве фазного провода воздушной линии напряжением 6–10 кВ // Наука XXI века: технологии, управле-ние, безопасность: сб. материалов науч.-практ. конф. [Электронное издание]. Курган: Изд-во Курган. гос. ун-та, 2017. С. 31–38.

Dhawas P.V., Bedekar P.P. Improvement in High Impedance Fault Detection of Primary Distribution Net-work Using Voltage and Current Sequence Components // 2020 IEEE 61th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON). Riga, Latvia, 2020. P. 1–6. DOI: 10.1109/RTUCON51174.2020.9316569

Analysis of the Negative Sequence Voltage to Detect Conductor Break in Distribution Systems / J.C. da Silva, G.N. Lopes, L.H.P.C. Trondoli, J.C.M. Vieira // 2021 IEEE Power & Energy Society General Meeting (PESGM). Washington, DC, USA, 2021. P. 01–05. DOI: 10.1109/PESGM46819.2021.9637945

Вакуумный реклоузер SMART15: Техническая информация. М.: АО «Таврида Электрик», 2024. 68 с. URL: https://www.tavrida.ru/upload/iblock/1a6/fb4x6llmvv0rev98dm8dyvpoqol7qp0c/TER_RecDoc_PG_8.pdf.

Siemens Vacuum Recloser 3AD. Medium-Voltage Equipment Catalog HG 11.42, 2016. 50 p. URL: https://assets.new.siemens.com/siemens/assets/api/uuid:8259a7dcc82300bcaff9ae63755dccb57091c758/catalog-hg-11-42-recloser-en.pdf.

Ershov A.M., Khlopova A.V., Sidorov A.I. Voltage Changes in Case of 6–10 kV Overhead Line Phase Wire Breakage in 6–10/0.38 kV Electic Network // 2018 International Conference on Industrial Engineering, Ap-plications and Manufacturing (ICIEAM). Moscow, Russia, 2018. P. 1–6. DOI: 10.1109/ICIEAM.2018.8728824

Определение мест обрыва и однофазных замыкания на землю в распределительных электрических сетях по параметрам режима на стороне 0,4 кВ понижающих подстанций / А.И. Федотов, Г.В. Вагапов, Н.В. Роженцова, Р.Э. Абдуллазянов // Промышленная энергетика. 2016. № 4. С. 34–40.

An Earth Fault Location Method Based on Negative Sequence Voltage Changes at Low Voltage Side of Distribution Transformers / D. Topolanek, M. Lehtonen, P. Tomana et al. // International Journal of Electrical Power & Energy Systems. 2020. Vol. 118. P. 1–8. DOI: 10.1016/j.ijepes.2019.105768

Определение поврежденного участка распределительной сети в режиме «двойное замыкание на землю» / Э.Ф. Хакимзянов, А.И. Федотов, Р.Г. Мустафин и др. // Известия высших учебных заведений. Про-блемы энергетики. 2016. № 7–8. С. 3–8.

Fault Segment Location for MV Distribution System Based on the Characteristic Voltage of LV Side /

D. Zhang, W. Zhang, C. Wang, X. Xiao // Electronics. 2023. Vol. 12. P. 1734. DOI: 10.3390/electronics12071734

Published

2024-01-01

How to Cite

[1]
Khlopova, A. and Gorozhankin, A. 2024. INCREASING ELECTRICAL SAFETY OF THE 10/0.38 kV NETWORK DUE TO CLARIFICATION OF THE SETTINGS OF PROTECTION DE-VICES IN THE EVENT OF THE 10 kV OVERHEAD LINE WIRE BREAK. Bulletin of the South Ural State University series "Power Engineering". 24, 1 (Jan. 2024), 99–108. DOI:https://doi.org/10.14529/power240111.

Issue

Section

Technological safety in electrical energy engineering